Skip to main content

Wire Size Calculator

Find the minimum copper or aluminum wire size for a given load using the NEC Table 310.16 ampacity values, with the 240.4(D) small-conductor rule applied.

The continuous load the circuit must carry, in amps.

Copper carries more current per size than aluminum.

Insulation temperature column in NEC Table 310.16. Terminations are usually limited to 75 C.

AI Financial Assistant

Beta

Ask questions about your calculation results

I can help you understand your results and explore your options. Try asking:

3 free questions per session

AI provides general information, not financial advice. Always consult a qualified professional.

How to Size Wire with NEC Table 310.16

The minimum conductor size for a circuit is the smallest wire whose allowable ampacity meets or exceeds the load. This calculator looks up the ampacity from NEC Table 310.16 for the chosen material and insulation temperature column, then returns the smallest size that carries your load.

The 60, 75, and 90 degree columns reflect the insulation rating. Most equipment terminations are listed for 75 degrees, so even with 90 degree wire you often size to the 75 degree column.

The 240.4(D) Small-Conductor Rule

NEC 240.4(D) caps overcurrent protection for small conductors regardless of the ampacity table: 15 amps for 14 AWG copper, 20 amps for 12 AWG copper, and 30 amps for 10 AWG copper, with lower values for aluminum. This calculator applies those caps so it never suggests a size the code would not allow on a standard breaker.

Do Not Forget Derating

Table 310.16 values assume not more than three current-carrying conductors and a 30 degree ambient. More conductors in a raceway or a hotter location reduces the usable ampacity under NEC 310.15. Size up when derating applies.

Frequently Asked Questions